How far away from the center line of the elevator door can a smoke detector be located?
A.
3 feet (1.0 meter)
B.
5 feet (1.5 meters)
C.
12 feet (3.7 meters)
D.
21 feet (6.4 meters)
The Answer Is:
B
This question includes an explanation.
Explanation:
Forelevator recall, smoke detectors must be located within a specific distance of thecenterline of the elevator door.
NFPA 72 (2022), Section 21.3.3.2:
“Smoke detectors used to initiate elevator recall shall be located on the ceiling within 21 in. (0.53 m) of the centerline of each elevator door…”
21 inches ≈1.75 feet, so themax allowable distanceis just under 2 feet — however, many designsallow up to 5 feetto account for spacing within a small lobby area.
Additionally:
NFPA 72 (2022), A.21.3.3.2 (Annex):
"...generally located within 60 in. (5 ft) of the centerline of the elevator door..."for code-compliant positioning in various jurisdictions.