Which of the following building fire alarm system components is required to be tested quarterly?
A.
duct detectors
B.
door electromechanical releasing devices
C.
supervisory signal devices
D.
water flow devices
The Answer Is:
D
This question includes an explanation.
Explanation:
According to NFPA 72: National Fire Alarm and Signaling Code, the following frequencies apply:
Waterflow devices (D): Must be tested quarterly.
Supervisory signal devices: Semiannual testing.
Duct detectors and door holders: Tested annually.
Thus, only water flow devices require quarterly testing.
[References:, NFPA 72: National Fire Alarm and Signaling Code, Table 14.4.3.2., The Joint Commission, Environment of Care Standards – Fire alarm system maintenance/testing., CHFM Candidate Handbook – Compliance domain.]